How Export Limiting Works
• Export limits are set during system commissioning
• Kora monitors net power flow continuously
• Excess generation is curtailed, redirected to storage, or load-managed
Common Use Cases
• Net Energy Metering (NEM) constraints
• Rule 21 export caps
• Non-export or zero-export sites
Verification
• Confirm export limits are active in commissioning interface
• Measure export under high-generation conditions
• Verify limits remain enforced during outages and transitions
Important Notes
• Export limits are utility-controlled, not homeowner-adjustable
• Improper CT installation will invalidate export limiting
• Changes may require utility re-approval